To calibrate the voltage and current offset, perform the following steps:
- Connect the GUI to view results for voltage and current.
- Configure the test source to supply the desired voltage and current.
- Using a low but non-zero value is recommended; for example, 120V and 0.5A.
- Click on the Manual cal. button.
- Input the difference from the expected input versus what the GUI is reading into the appropriate fields.
Note: AC current offset is in microamps and AC voltage offset is in millivolts.